Structure: | Mobile, Fix, Fully Enclosed, Trailer Type, Are Ok |
---|---|
Usage: | Solid-Liquid Separation, Oil Impurities, Oil-Water Separator, Air Filter, Oil and Gas Separation, Transformer Evacuation |
Type: | Effective Filtration, Remove Water and Particles |
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Parameters | Model Unit |
ZYD-U-100 | ZYD-U-150 | ZYD-U-200 | ZYD-U-300 | |
Flow Rate | L/H | 6000 | 9000 | 12000 | 18000 | |
Ultimate Vacuum Degree | Pa | ≤ 2 | ||||
Working Vacuum Degree | Pa | ≤ 30 | ||||
Working Discharge Pressure |
MPa | ≤ 0.5 | ||||
Temperature Control Range |
ºC | 20 ~ 80 | ||||
Operation Temperature | ºC | 40 ~ 65 | ||||
Power Supply | 380V, 50Hz, 3 phases (or as per your requirements) | |||||
Ambient Temperature | -25 ~ 55ºC | |||||
Working Noise | dB(A) | 65 ~ 90 | ||||
Heating Power (adjusted available) |
KW | 66 | 90 | 132 | 180 | |
Total Power | KW | 72 | 105 | 150 | 200 | |
Inlet/Outlet | mm | Φ32 | Φ40 | φ50 | φ65 | |
Weight | Kg | 1200 | 1600 | 2200 | 3000 | |
Dimension | mm | 2200×1700×2450 | 2500×1950×2500 | 2850×2050×2600 | 3600×2500×3100 | |
Oil Result after Filtration | Moisture (Water Content) ≤ 3 PPM | |||||
Gas Content ≤0.01% (Vol) | ||||||
Impurities Degree (Filtration precision) ≤ 1 micron (no free carbon) | ||||||
Breakdown Voltage (Dielectric Strength) ≥73 KV | ||||||
Flash Point ≥145ºC | ||||||
Granularity 5 ~ 50μm (in 100ml oil sample) ≤ 500 Nos | ||||||
Cleanliness ≤NAS 1638 Grade 6 |
Suppliers with verified business licenses