• Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
  • Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
  • Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
  • Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
  • Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
  • Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer

Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer

Appliance: for Testing Dissolved Gas in The Oil
Ray Type: X-Ray Spectrometer
Gaspath System: Double
Customization:
Shipping Cost:

Estimated freight per unit.

about shipping cost and estimated delivery time.
Payment Method: visa mastercard discover JCB diners club american express T/T
  Initial Payment Full Payment
Currency: US$
Return&refunds: You can apply for a refund up to 30 days after receipt of the products.
From payment to delivery, we protect your trading.
Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer pictures & photos
Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
US $9,800-36,500 / Piece
Min. Order: 1 Piece
Manufacturer/Factory, Trading Company
Gold Member Since 2020

Suppliers with verified business licenses

Secured Trading Service
Chongqing, China
Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
to see all verified strength labels (21)

Basic Info.

Model NO.
FT-2010SD
Detector
Tcd, Double Fid and Methane Conversion Oven
Energy Resolution
0.5
Certification
CE, ISO, IEC
Chromatography Type
Gas Chromatography
Application Standard
Complies to GB7252-2001, and ASTM D2887.
Temperature Control Precision
+- 0.1 Deg C
Gas Analyzing
H2, O2, N2, CH4, C2h2, C2h4, C2h6, Co, CO2
Power Supply
220V, 50Hz
Environmental Condition
5 ~ 35 Degree C
Relative Humidity
Less Than 80%
Condition
100% Brand New
Power Consumption
2.5 ~ 3kw
Warranty
1 Year
After-Sales Services Provided
Field Installation, Commision, Training
Transport Package
in Standard Exportation Plywood Case
Specification
730 * 650 * 630mm
Trademark
FUOOTECH
Origin
Chongqing, China
HS Code
90278099
Production Capacity
5200 PCS/Year

Product Description

Series FT-2010SD DGA Analysis System
Series FT-2010SD Power system Dedicated Insulation Oil and Gas Chromatography Analysis System

FT-2010SD Power system Dedicated Insulation Oil and Gas Chromatography Analysis System runs by computer automatic control, all-keyboard operation and large-screen liquid crystal display according to the requirements of power system "dissolved gas component determination in insulation oil (chromatography)", and is characterized by high-precision temperature control, stable and reliable performance, high sensitivity, good reproducibility and so on.

     The analyzer adopts double-pillar parallel shunt system ,equipped with TCD, double FID and methane conversion oven, and could achieve total analysis of nine components (H2, O2, N2, CH4, C2H2, C2H4, C2H6, CO, CO2) of dissolved gas in insulation oil by one time.
Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer

   The analyzer can be employed for internal fault detection of power system oil and gas equipments, cooling medium analysis of hydrogen-cooled generators, impurity analysis of sulfur hexafluoride, the boiler flue gas analysis, gas analysis and environmental monitoring analysis. Due to its employment not only for special analysis, but also for general analysis, the analyzer becomes the most effective gas analytical instrument in petroleum, chemical engineering, mining and other systems.
 
Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer

Major Characteristics:
 
1. Computer-keyboard operation, easy to operate.
2. High precision and sensitivity, good reproducibility
3. Stable and reliable analyzing performance
4. Automatic analysis process, simple operation
5. Large LCD screen
6. Test Standard: complies to GB7252-2001, and ASTM D2887standard.


Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
1.  Main technical specification:
1.1  Temperature Control
Temperature range
 Column chamber: room temperature +15ºC ~ 399ºC
Vaporizing chamber: room temperature +30ºC ~ 399ºC
Conversion furnace :room temperature +30ºC ~ 399ºC
Thermal conductivity detector: room temperature +30ºC ~ 399ºC
Hydrogen flame detector :room temperature +30ºC ~ 399ºC
Temperature control precision: ±0.1ºC

1.2  Thermal conductivity detector
Sensitivity: minimum detectable concentration of hydrogen≥5μl/L
Noise: ≤0.05mv
Drift: ≤0.15mv/30min
1.3  Hydrogen Flame Detector
Minimum detectable concentration of hydrocarbon ≥ 5 μl/L
Minimum detectable concentration of CO,CO2 ≥ 5 μl/L
Noise: ≤ 0.05 mv
Drift: ≤ 0.15 mv/30min
1.4  Whole machine start-up time:  less than 3 hours

2.  Main performance characteristics:
2.1  Computer-keyboard operation
This realizes five heating zone temperature control, detector control, over-temperature protection, "zero" degree protection, air break protection and other functions, so as to protect the chromatographic column and thermal conductivity rhenium tungsten filament most effectively.
2.2  Large-screen liquid crystal display
It could display a large amount of information intuitively and clearly.
2.3  Advanced chromatography process
Based on only one injection and three-detectors analytical process, the analyzer greatly increases detection sensitivity of hydrocarbon gas. Double hydrogen flame setting also reduces the detection impact caused by the gas content differences.

3.  Working conditions
3.1  Normal instrument working conditions
Environmental condition:5ºC ~ 35ºC
Relative Humidity:≤80%
Power supply:220V±10% 50Hz±0.5Hz
3KW power provided.
No strong electromagnetic interference, corrosive gas and strong shock in the surroundings.


3.2  Gas source
    Air purity:  ensure the purity of carrier gas and hydrogen is more than 99.99%, the air to be used is  

purified and air generator function in dust, oil and water removal.
   
Output pressure of steel cylinder relief valve: nitrogen 0.35MPa, hydrogen 0.25MPa, air 0.35MPa
 
Please replace steel cylinder timely when output pressure fell below 2MPa.


3.3  Ground wire
   To ensure personal safety and instrument performance, the instrument must be reliably linked to the land.  

It is suggested to bury the ground wire in the soil 1 meter below.


PACKING & SHIPPING & PAYMENT

Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer
Fuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography AnalyzerFuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography AnalyzerFuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography AnalyzerFuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography AnalyzerFuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography AnalyzerFuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography AnalyzerFuootech FT-2010SD Dga Analysis System Oil Chromatographic Analyzer Transformer Oil Gas Chromatography Analyzer

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now